J045--NEW REPLACE AHU-1 HVAC COIL FOR PHARMACY Intent to Sole Source
VETERANS AFFAIRS, DEPARTMENT OF
About this opportunity
Page 1 of 3 STATEMENT OF WORK PART A GENERAL INFORMATION A.1 INTRODUCTION The Hershel Woody Williams VAMC located at 1540 Spring Valley Drive, Huntington WV, 25704 needs to replace AHU-1 HVAC coil that serves pharmacy. A.2 BACKGROUND The AHU-1 pharmacy chiller coil has failed: this unit serves inpatient IV and chemo rooms. Ties into Johnson Controls building automation system. A.3 SCOPE OF WORK Vendor will provide all labor, material, equipment, tools, and supervision necessary to meet the Statement of Work below. STATEMENT OF WORK PART B WORK REQUIREMENTS B.1 Tasks to be accomplished: Provide base unit loose coil (4420) heating; type ½ BDW, HEIGHT: 32.5 WIDTH 33, ROWS 1, FPI: 11; COIL HAND LEFT; FIN MATERIAL: ALUMINUM, FIN THICKNESS: .008 in., tube wall thickness: .016 in Provide base uni...