NVARNG AASF Fuel Farm Pump and Motor Repair
DEPT OF DEFENSE
Who can apply
Total Small Business Set-Aside (FAR 19.5). SBA
About this opportunity
Amendment 0001 Questions from Industry with responses (also see attachment "W9124X26QA006 Questions and Answers") Request For Information (RFI) 1: What is the make and model of the pumping unit? Gorman-Rupp Pumps Model No. RD3A31 BAR~ RFI 2: Motor nameplate data/specifications. The data plate is weather worn, but appears to state: NO C97000007 SER # C1904040472 SPEC 12-0000-0485 CAT. No. H.P. 40 T. CODE T3C VOLTS 460 AMPS 44 R.P.M. 3545 HZ 60 PH 3 CLASS H SER. F. 1.15 DES B CODE G RATING 4C AMB-CONT FRAME 324TS NEMA NOM EFF 92.4% UABLE @ 208V A PF 91% BALDOR ELECTRIC CO. FT. SMITH, AR U.S.A. NP0015XPSLEV RFI 3: Confirm whether the unit is mobile or installed at a fixed refueling rack location. Installed at a fixed refueling rack location. RFI 4: Drive configuration. Coupled system. RFI 5: ...