Z1DA--598-19-112 Replace Underground 15kV Feeders and Transformers-NLR
VETERANS AFFAIRS, DEPARTMENT OF
About this opportunity
36C25626R0023 RFI Answers Proposal RFI #1 Drawing E502 (partial one-line) shows 5KV switchgear feeding transformers and 15KV switchgear feeding transformers. Is that accurate? What is the primary voltage of all the transformers? Can we get that included in the table on drawing E501. Use drawings E401-E406. Drawing # 502 detail 4 show existing 5KV switch gear at building 88 has been removed. Everything is 15KV. Proposal RFI #2 Can we get a one-line that shows all the transformers and manholes? Similar to drawing E502 but will all the transformers and manholes. See the attached marked up E502 that shows the transformers I was able to deduce by the buildings they are feeding (per the table in E501). Note that one of the manholes we looked at during the site visit was outside of Building 69, a...