J041--36C249-26-AP-1581 Proj. 603-26-905 Refurbish AHUs (Eng.) (VA-26-00042582)
VETERANS AFFAIRS, DEPARTMENT OF
Who can apply
Service-Disabled Veteran-Owned Small Business Set Aside. SDVOSBC
About this opportunity
The purpose of this amendment is to post 1) Questions and Answers to Solicitation 36C24926Q0231 LOU AHU Refurbish Questions and Answers Part 2 and 2) attach the Vendor Site visit sing in sheet 36C24926Q0231 LOU AHU Refurbish Pt 2 Questions Chilled Water piping and Steam Piping connections are behind the AHU and are not accessible. Answer: Yes, they are behind the AHU, they are difficult to access not inaccessible. The Unit is a MCQuay Unit. MCQuay Units are no longer made and coils to fit this unit exactly will be difficult. Would it be advised to replace this unit with a new unit for performance satisfaction? Answer: No, McQuay was purchased in 2006 by Daikin and Daikin still makes OEM replacement coils.